FPC Series
Functions
- Level control mode – Level empty operation controlled by up to 5 float switches: Low level, duty stop, duty start, standby start and high level.
- Pressure control mode – Pressure boost operation controlled by up to 3 pressure switches: Duty start, standby start and low pressure.
- Duty sharing and alternation – Duty pump alternates on pump start and after 30 minutes of continuous running in alternation mode, or 6 hours of accumulated running in recirculation mode.
- Staggered pump start – Prevents excessive current draw and reduces water surge.
- Manual pump control – Manual pump mode with optional 5-minute timeout to revert to auto mode.
- System enable input – Enables and disables the system in auto mode.
- Static duty mode – No duty alternation, for applications using smaller duty pump that always starts first.
- Smart chirp alarm – Audible alarm automatically silences after 5 minutes if not muted, then chirps every 5 minutes.